Dust and drip proof.(designed to IEC 529 IP54) In addition to the facility for precision measurement, test leads for simplified two wire measuring system also supplied as standard accessories. (unit can be hung from the neck for simplified measurement) Designed to meet IEC 61010-1 safety standard. Capable of measuring earth voltage. Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance. Small and lightweight. Shock resistant new case material. 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
Measurement Ranges Earth Resistance: Earth Voltage 50,60Hz: 0~200V AC Accuracy Earth Resistance: 2%rdg0.1 (20range) Earth Voltage: 1%rdg4dgt Overload Protection Earth Resistance: 280V AC for 10 seconds across 2 of the 3 terminals Earth Voltage: 300V AC for 1 minute Safety Standard IEC 61010-1 300V Pollution Degree 2, IEC 61557 Applicable Standards IEC 60529 IP54 Withstand Voltage 3700V AC for 1 minute Power Source R6P (AA) (1.5V) 6 Dimensions 105(L) 158(W) 70(D)mm Weight 550g approx. Accessories 7095A (Earth resistance test leads) 1set (red-20m, yellow-10m, green-5m) 8032 (Auxiliary earth spikes) 1set 7127A (Simplified measurement probe) 1set R6P (AA) 6 Neck strap Instruction Manual Carrying Case : 4105A (Soft case)