Cells Per Unit 6 Voltage Per Unit 12 Nominal Capacity 7Ah@20hour-rate to 1.75V per cell @25℃ Weight Approx. 1.95 Kg (Tolerance±5.0%) Max. Discharge Current 70A (5 sec) Internal Resistance Approx. 32 mΩ Terminal F1/F2 Max. Charging Current 2.1 A Container Material A.B.S. UL94-HB, UL94-V0 Optional. Operating Temperature Range Discharge: -20℃~60℃ Charge: 0℃~50℃ Storage: -20℃~60℃ Normal Operating Temperature Range 25℃±5℃ Standby Use Voltage 13.7 V~13.9 V @ 25℃ Cycle Use Voltage Self Discharge RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25℃ and then recharging is recommended. Monthly Self-discharge ratio is less than 3% at 25℃.Please charge batteries before using. Design Life 6~8 years (Float charging) Reference Capacity C3 5.42AH C20 7.00AH Short Circuit Current 350A Specification C5 6.11AH C10 6.54AH 14.6 V~14.8 V @ 25℃ The battery must be fully charged before the capacity test. The C20 should reach 95% after the first cycle and 100% after the third cycle. Dimensions Temperature Compensation: -3mV/℃/Cell Temperature Compensation: -4mV/℃/Cell